Test Kit Chloride

Test Kit Chloride

Determination of chloride. Range 0 - 400 ppm.

Product description

Drops of reagent BC2

Chloride as mg/l Cl

Notes

1

20

Maintain daily blowdown

2

40

3

60

4

80

5

100

Acceptable chlorides in low-pressure boiler

6

120

7

140

8

160

9

180

10

200

11

220

12

240

13

260

14

280

15

300

16

320

Reduce chlorides by increased blowdown

17

340

18

360

19

380

20

400

Note: If measuring boiler water it is possible to use the completed alkalinity test sample and follow instructions from step 2 above.

Equipment & reagents

EDT018 65 ml Plastic Test Bottle
SDT023 BC1/CC1 Indicator
SDT026 BC2 High Range Titrant

Testing procedure

  • 1. Fill the test jar with 20 ml of cooled sample. Note: If measuring boiled water, use the tested sample from step 3 of the alkalinity test.
  • 2. Add 4 drops of reagent BC1/CC1. The sample will turn yellow.
  • 3. Add drops of reagent BC2 one at a time until a pale orange colour appears. Count the number of drops used. Each drop is equivalent to 20 mg/l chloride.
This information is not to be taken as a warranty or representation for which Vecom Marine assumes legal responsibility.