Product description
TEST KIT NITRITE is suitable for measuring nitrite levels in cooling water systems. Designed to accompany COOLTREAT NCLT in cooling water systems.
|
Number of uses: Between 176 – 187 |
Recommended use with: |
Directions for use
1. Place a cold 0.5 ml sample in the test tube using the plastic syringe provided and add 2 – 3 ml of nitrite free water (e.g. deionised or drinking water).
2. Add 4 drops of reagent N1; the sample will turn an orange colour.
3. Add drops of reagent N2M one at a time with mixing until the orange colour changes to pale blue. Count the number of drops used.
4. Each drop is equivalent to 200 mg/l as nitrite (NO2).
Drops of N2 reagent |
Nitrite as mg/l NO2 |
Notes |
1 |
200 |
The product is under-treated for all engine types and should be added to correct the nitrite level. |
2 |
400 |
|
3 |
600 |
|
4 |
800 |
|
5 |
1000 |
|
6 |
1200 |
|
7 |
1400 |
|
8 |
1600 |
|
9 |
1800 |
Sufficient product for normal speed engines using water that contains up to 50 ppm chloride |
10 |
2000 |
|
11 |
2200 |
|
12 |
2400 |
Sufficient product for normal speed engines using water that contains up to 50 ppm chloride Sufficient product for high speed engines using water that contains up to 50 ppm chloride |
13 |
2600 |
|
14 |
2800 |
|
15 |
3000 |
Sufficient product for high speed engines using water that contains up to 50 ppm chloride |
16 |
3200 |
|
17 |
3400 |
Instruction video:
Test Kit Nitrite contents
• 1x 10 ml Test Tube
• 1x 2 ml Syringe
• 1x 30 ml N1 Indicator
• 4x 30 ml N2M Titrant
Features & Benefits
- Easy to use
- Reliable & accurate results
- Easy management & storing design
- Uniform reagent consumption
- Reagents in excepted quantities making the kit normal-post sendable